Exit Width and Egress Door Calculator
Enter the occupant load and the kind of space. See the aggregate exit width for doors, corridors, ramps and stairs, how many exits and doors you need, and the travel distance limit.
Preliminary planning figure only. The architect, the fire protection engineer and the permit set govern the means of egress.
0 mm
| Element | mm per person | Aggregate width (mm) | Least single width (mm) |
|---|
Ardenvale carries out tenant improvements, commercial interior renovations and change of use construction across the Greater Toronto Area, including new and relocated doors, corridors and exit routes.
Tenant improvements · Commercial interior renovation · Change of use construction
Get a quote for your tenant improvement or change of useUse this tool from any AI assistant
Paste this link into ChatGPT, Claude, Gemini, Copilot, Perplexity or any AI assistant and ask it to read the result:
Change the numbers in the link to match your project. All tools for AI assistants.
Sources and assumptions
- Last checked 2026-11-09, against the 2024 Building Code Compendium on ontario.ca.
- 2024 Ontario Building Code (O. Reg. 163/24), Division B, Part 3 Sentences 3.4.2.1.(1) and (2) with Tables 3.4.2.1.-A and -B; 3.4.2.3.(1); 3.4.2.5.(1) and (2); 3.4.3.1.; 3.4.3.2.(1), (2), (7) and (8) with Tables 3.4.3.2.-A and -B; 3.3.1.5.(1). Projects permitted under the earlier Ontario Regulation 332/12 may be subject to that version.
- Table 3.4.2.1.-A values used (not sprinklered throughout) Maximum floor area and travel distance for one exit: Group A 150 m² and 15 m; Group C 100 m² and 15 m; Group D 200 m² and 25 m; Group E 150 m² and 15 m; Group F Division 2 150 m² and 10 m; Group F Division 3 200 m² and 15 m.
- Table 3.4.2.1.-B values used (sprinklered throughout) Maximum floor area for one exit with a travel distance of not more than 25 m: Group A 200 m²; Group C 150 m²; Group D 300 m²; Group E 200 m²; Group F Division 2 200 m²; Group F Division 3 300 m².
Changing a space and need the exits to work?
Send us the plans or a short description. We will arrange a site review and return a clear written quote.
Ardenvale carries out tenant improvements, commercial interior renovations and change of use construction across the Greater Toronto Area, including new and relocated doors, corridors and exit routes. Tenant improvements · Commercial interior renovation · Change of use construction
Frequently asked questions
How is the required exit width worked out?
Sentence 3.4.3.2.(1) multiplies the occupant load by a width per person: 6.1 mm for doorways, corridors, passageways and ramps with a slope of not more than 1 in 8; 8 mm for stairs with a rise of not more than 180 mm and a run of not less than 280 mm; 9.2 mm for steeper ramps and other stairs. Care, and care and treatment, occupancies use 18.4 mm per person.
Why does the tool say at least two exits?
Sentence 3.4.2.1.(1) requires at least two exits from every floor area intended for occupancy. Sentence 3.4.2.1.(2) allows one exit in a building of not more than two storeys when the occupant load is not more than 60 and the floor area and travel distance stay within Table 3.4.2.1.-A, or, with sprinklers throughout, a travel distance of not more than 25 m and a floor area within Table 3.4.2.1.-B. Enter the area and the travel distance to test it.
Do exits add together?
Where two or more exits converge, the required width is cumulative (Sentence 3.4.3.1.(2)). Where more than one exit is required, each exit is treated as contributing not more than one-half of the required width (Sentence 3.4.3.2.(7)).
What is the least width of a single door, corridor or stair?
Table 3.4.3.2.-A sets 850 mm for a doorway, 1,100 mm for a corridor or ramp, and 900 mm for a stair serving not more than 2 storeys above or 1 storey below the lowest exit level, 1,100 mm for a stair serving more. Care occupancies have higher minimums where a ramp, stair or doorway serves sleeping rooms (Table 3.4.3.2.-B).
How far can someone travel to reach an exit?
Sentence 3.4.2.5.(1) allows 25 m in a high-hazard industrial occupancy, 40 m in business and personal services, 45 m in a floor area sprinklered throughout, and 30 m in the other cases. Sentence 3.4.2.5.(2) can relax this where the exits are along the perimeter and not more than 60 m apart. The architect confirms which clause applies.
Does this cover arenas, stadia and exit stairs in detail?
No. Group A, Division 4 occupancies use different widths per person, and fire separations, exit stair construction and the rest of Part 3 are separate. Use the result as an early planning check.