Washroom Fixture Calculator
Estimate the minimum number of water closets and lavatories for each sex in an office or shop, using the Ontario Building Code tables for business and mercantile occupancies.
Preliminary planning figure only. Accessible and universal washroom rules apply separately. The architect, the engineer and the permit set govern.
0 water closets
| Fixture | Male | Female |
|---|
Ardenvale renovates washrooms and fits out offices and shops across the Greater Toronto Area.
Get a quote for your washroom renovationUse this tool from any AI assistant
Paste this link into ChatGPT, Claude, Gemini, Copilot, Perplexity or any AI assistant and ask it to read the result:
Change the numbers in the link to match your project. All tools for AI assistants.
Sources and assumptions
- Ontario Building Code (O. Reg. 163/24), Division B, Subsection 3.7.4, Plumbing Facilities Articles 3.7.4.2, 3.7.4.7 and 3.7.4.8 and Tables 3.7.4.7 and 3.7.4.8 were read from the 2024 Building Code Compendium published on ontario.ca. Projects permitted under the earlier Ontario Regulation 332/12 may be subject to that version.
- Table values used Water closets for each sex: up to 9 persons, 1; 10 to 24, 2; 25 to 49, 3; 50 to 74, 4; 75 to 100, 5; over 100, 6 plus 1 for each additional increment of 30 persons of each sex over 100. Mercantile public: at least one for each 300 males and one for each 150 females.
Renovating washrooms or fitting out a new space?
Send us the plans or a short description. We will arrange a site review and return a clear written quote.
Ardenvale renovates washrooms and fits out offices and shops across the Greater Toronto Area. Washroom renovation · Office fit-out
Frequently asked questions
How does the Code count the people to design for?
Sentence 3.7.4.2.(1) uses the occupant load determined under Subsection 3.1.17, except that in a Group D (business and personal services) occupancy the area per person is 14 square metres. Enter that number of persons here, or use our occupant load calculator for the table value.
How are men and women counted?
Water closets are provided for each sex assuming the occupant load is divided equally between males and females, unless the proportion expected in the building can be determined with reasonable accuracy. The split is an input here so you can change it.
Can urinals replace water closets?
For males, urinals may be substituted for water closets and counted toward the total provided the number of urinals is not more than two-thirds of the required number in most occupancies. If only two water closets are required for males, one urinal may be substituted for one of them. The tool shows the limit.
Does this cover accessible and universal washrooms?
No. Barrier-free washroom requirements, including the universal washroom described in Sentence 3.8.3.12.(1), are separate and can change how the fixtures are arranged. Restaurants fall under Article 3.7.4.3 and are not calculated here.
Are lavatories counted too?
Yes, in a simple form. Sentence 3.7.4.2.(6) calls for at least one lavatory in a room with one or two water closets or urinals and one more for each additional two. The tool applies that rule per sex.
How are partial increments handled above 100 persons?
The tables add one water closet for each additional increment of 30 persons of each sex above 100 but do not say how a partial increment is treated. This tool rounds a partial increment up, the cautious choice for planning. Confirm with your architect.